Rated operation voltage Ue: AC 240V
Rated insulation voltage Ui 500V
Action characteristics: when the applied voltage ≤35% Ue, the product should prevent circuit breaker from closing; when 35% Ue≤ applied voltage ≤70% Ue, the product should operate and drive the circuit breaker open; when the applied voltage ≥85% Ue, the product should be able to close. The applied voltage should not exceed 110%Ue. Life: the operating life of the release is ≥ 4000 cycles.